The PWRcell is a hybrid inverter system integrating solar PV input, battery storage, and grid interaction. Error 7100 suggests a failure in the inverter's grid-tie functionality. This involves AC voltage sensing, frequency synchronization (60Hz), anti-islanding protection (UL 1741 SA), and power factor correction. The inverter's control board monitors grid parameters via voltage and current transformers (VT/CT) and uses this data to modulate the output waveform. A communication failure between the grid sensing circuitry and the main controller, or a fault in the grid-tie relay, can trigger Error 7100. Grid disturbances outside of the inverter's operating window can also trigger the fault.