Recommended Action:
-
1Determine the maximum continuous current (I_max) of both the EG4 Lifepower4 battery and the connected inverter from their respective datasheets.
-
2Calculate the minimum fuse ampacity: I_fuse = 1.25 * I_max (NEC 240.4(B) often requires using the next standard fuse size up if the calculation does not result in a standard size).
-
3Select a fuse with an ampacity rating equal to or slightly higher than the calculated I_fuse, but not exceeding the maximum fuse rating specified by EG4 for the Lifepower4 battery. Consult the EG4 documentation.
-
4Verify that the fuse voltage rating is at least equal to the maximum DC voltage of the battery system (e.g., 58.4V for a 48V system).
-
5Use a multimeter to verify voltage drop across the fuse holder is minimal (should be close to 0V). High voltage drop indicates a poor connection. Tighten connections as needed. Only qualified personnel should perform these steps with proper PPE and procedures.
-
6Inspect the fuse holder for corrosion or damage. Replace if necessary.
-